switchgear and controlgear
CFIHOS
TagAndEquipmentClass
ID: CFIHOS-30000370
Faça login para ver esta definição.
Hierarchy
Properties / Attributes (169)
| Name | Data Type | Unit / Valid values | Required | Definition |
|---|---|---|---|---|
| accessibility type as per IEC 62271-200 | Text |
— | Optional | The high-voltage switchgear and controlgear accessibility type in accordance with IEC 62271-200. |
| air circuit breaker auxiliary contact provision | Text |
— | Optional | The number of auxiliary contacts required for each air circuit breaker (NO-normally open, NC-normally closed). |
| assumed loading factor distribution - 1 circuit | Text |
— | Optional | The assumed loading factor value given for a section containing only 1 distribution circuits in accordance with IEC 61439-2:2020. |
| assumed loading factor distribution - 10 or more circuits | Text |
— | Optional | The assumed loading factor value given for a section containing more than 10 distribution circuits in accordance with IEC 61439-2:2020. |
| assumed loading factor distribution - 2 and 3 circuits | Text |
— | Optional | The assumed loading factor value given for a section containing 2 to 3 distribution circuits in accordance with IEC 61439-2:2020. |
| assumed loading factor distribution - 4 and 5 circuits | Text |
— | Optional | The assumed loading factor value given for a section containing 4 to 5 distribution circuits in accordance with IEC 61439-2:2020. |
| assumed loading factor distribution - 6 and 9 circuits | Text |
— | Optional | The assumed loading factor value given for a section containing 6 to 9 distribution circuits in accordance with IEC 61439-2:2020. |
| assumed loading factor electric actuator (MOV) | Text |
— | Optional | The assumed loading factor electric actuator (MOV). |
| assumed loading factor motors rated greater than 100 kW | Text |
— | Optional | The assumed loading factor motors rated greater than 100 kW. |
| assumed loading factor motors rated less than or equal to 100 kW | Text |
— | Optional | The assumed loading factor motors rated less than or equal to 100 kW. |
| auxiliary cable direction of external conductors | Text |
— | Optional | The direction of the auxiliary cable of external conductors. |
| auxiliary cable entry direction | Text |
— | Optional | The required auxiliary cable entry direction. |
| auxiliary cable external conductor type | Text |
— | Optional | The conductors type of the external auxiliary cable. |
| auxiliary circuits voltage | Number |
volt | Optional | The auxiliary circuit rated voltage. |
| average relative humidity | Number |
percent | Optional | The high-voltage switchgear and controlgear average value of the relative humidity measured over a period of 24h in accordance with IEC 62271-1. |
| back-to-wall switchgear configuration required | Boolean |
— | Optional | The switchgear back-to-wall configuration. |
| bus coupler switching device requirement | Text |
— | Optional | The type of bus coupler switching device requirement. |
| cable termination chamber location | Text |
— | Optional | The location of cable termination chamber. |
| capacitive breaking capability class of switches | Text |
— | Optional | The high-voltage switchgear and controlgear capacitive breaking capability class of switches in accordance with IEC 62271-103. |
| circuit breaker condition monitoring | Text |
— | Optional | Specify if an integrated circuit breaker condition monitoring system is required. |
| circuit breaker spring charging motors voltage | Text |
— | Optional | The circuit breaker spring charging motor rated voltage. |
| circuit breaker switching medium | Text |
— | Optional | The circuit breaker switching medium. |
| circuit-breaker mechanical endurance class | Text |
— | Optional | The high-voltage switchgear and controlgear mechanical endurance class of circuit breakers in accordance with IEC 62271-100. |
| circuit-breaker restrike class | Text |
— | Optional | The high-voltage switchgear and controlgear circuit-breaker restrike class in accordance with IEC 62271-100. |
| circuit-breaker system class | Text |
— | Optional | The high-voltage switchgear and controlgear circuit-breaker system class in accordance with IEC 62271-100. |
| closing and opening control voltage | Text |
— | Optional | The high-voltage switchgear and controlgear closing and opening control voltage in accordance with IEC 62271-1. |
| closing and opening indication voltage | Text |
— | Optional | The high-voltage switchgear and controlgear closing and opening indication voltage in accordance with IEC 62271-1. |
| closing and tripping devices voltage | Text |
— | Optional | The high-voltage switchgear and controlgear closing and tripping device voltage in accordance with IEC 62271-1. |
| communication protocol | Text |
— | Optional | The digital communication system (if any), such as HART, Foundation Fieldbus or Profibus |
| communication protocol availability class | Text |
— | Optional | The high-voltage switchgear and controlgear availability class in accordance with IEC 62271-3. |
| communication protocol performance class | Text |
— | Optional | The high-voltage switchgear and controlgear conformance class in accordance with IEC 62271-3, 5.2. |
| compartment doors locking facility | Text |
— | Optional | The means of access control with regards to closed compartments covers and doors. |
| compartment insulating medium | Text |
— | Optional | The equipment technical requirement with regards to insulation medium. |
| conductor material | Text |
— | Optional | The material of the external conductor. |
| conformity assessment system level | Text |
— | Optional | The Conformity Assessment System (CAS) class letter in accordance with IOGP specification and obligatory requirements. |
| contactor control power source | Text |
— | Optional | The contactor control power source configuration. |
| contactor switching medium | Text |
— | Optional | The contactor switching medium. |
| country region | Text |
— | Optional | Geographic location of the project within a country which will determine the applicability of local regulatory requirements. |
| earth fault front of compartment reset | Text |
— | Optional | Specify if a earth fault front of compartment reset is required. |
| earthing device operator location | Text |
— | Optional | The equipment's required earthing device operator location. |
| earthing switch mechanical endurance class | Text |
— | Optional | The earthing switch mechanical endurance class. |
| earthing system | Text |
— | Optional | The type of earthing system for which the assembly will be installed. |
| ECMS simulation test requirement | Text |
— | Optional | Specify if an integrated internal arc-fault detection system is required. |
| electrical control interface media | Text |
— | Optional | The electrical control interface (ECMS) media requirements. |
| electrical control interface network redundancy | Text |
— | Optional | The electrical control interface (ECMS) network redundancy. |
| electrical endurance class | Text |
— | Optional | The high-voltage switchgear and controlgear classification of earthing switches and circuit-breakers for short-circuit making in accordance with IEC 62271-102. |
| electromagnetic compatibility environment | Text |
— | Optional | The low voltage switchgear and controlgear electromagnetic compatibility (EMC) environment in accordance with IEC 61439-1:2020. |
| elevation over mean sea level | Number |
metre | Optional | Plant elevation over mean sea level. |
| enclosure floor surface | Text |
— | Optional | Specify whether the floor surface below the installed assembly may be considered as part of the enclosure. |
| energy and maximum demand metering accuracy | Text |
— | Optional | The energy and maximum demand metering accuracy class. |
| environmental location | Text |
— | Optional | The environmental installation location of the equipment. |
| equipment access | Text |
— | Optional | Specify if access to the equipment is restricted to authorized persons. |
| equipment integration location | Text |
— | Optional | Specify if the equipment integration site differs from the end usage site, associated transport/logistic options and conditions at the integration site this shall be identified. |
| explosion protection gas group | Text |
— | Optional | Specify the gas group classification of the physical object in accordance with IEC/EN 60079-20 |
| explosion protection temperature class | Text |
— | Optional | Specify the temperature classification of the physical object in accordance with CENELEC EN50014 |
| explosion protection zone | Text |
— | Optional | Specify the hazardous zone in which the functional or physical object is expected to operate. |
| explosion rated item | Boolean |
— | Optional | An indicator that an equipment has been classified as safe for use in hazardous areas |
| facility to remotely test withdrawn functional units | Text |
— | Optional | Specify if facility to remotely test withdrawn functional units are required. |
| glanding requirement | Text |
— | Optional | Specify if special glanding is required. |
| HV connection compartment space heater requirement | Text |
— | Optional | Specify if a space heater is required in the high voltage compartment. |
| IEC TR 61641:2014 arcing class | Text |
— | Optional | The equipment's arcing class in accordance with IEC TR 61641:2014. |
| IED brand | Text |
— | Optional | Specify if the IED brand is manufacturers standard or other. |
| IED remote configuration via ECMS | Text |
— | Optional | Specify if the IED remote configuration via ECMS requirements. |
| IED to generator control panel interface media | Text |
— | Optional | The IED to generator control panel interface media requirements. |
| IED to generator control panel interface protocol | Text |
— | Optional | The IED to generator control panel interface protocol requirements. |
| IED to power management system interface media | Text |
— | Optional | The IED to power management system interface media requirements. |
| IED to power management system interface protocol | Text |
— | Optional | The IED to power management system interface protocol requirements. |
| IED to power management system network redundancy | Text |
— | Optional | The IED to power management system interface network redundancy requirements. |
| impact protection | Text |
— | Optional | The impact protection with regards to impact energy according to IEC 62262. |
| incoming (supply) unit entry of external conductors | Text |
— | Optional | The incoming (supply) unit direction of external conductors. |
| incoming (supply) unit external conductor type | Text |
— | Optional | The termination details for incoming supply conductors. |
| incoming cable entry direction | Text |
— | Optional | The required incoming cable entry direction. |
| incoming unit switching device requirement | Text |
— | Optional | The type of incoming unit switching device requirement. |
| ingress protection | Text |
— | Optional | Specify the degree of ingress protection for the physical object in accordance with IEC/EN 50629 or NEMA, UL and CSA type rating. |
| integrated internal arc-fault detection system | Text |
— | Optional | Specify if an integrated internal arc fault detection system in accordance with IEC TS 63107 is required. |
| interlocking / intertripping interface media | Text |
— | Optional | The discrete hardwired interlocking / intertripping media requirements. |
| interlocking / intertripping interface protocol | Text |
— | Optional | The discrete hardwired interlocking / intertripping protocol requirements. |
| internal arc-fault control device type | Text |
— | Optional | The internal arc-fault control device type. |
| internal arc-fault reduction device type | Text |
— | Optional | The internal arc-fault reduction device type. |
| internal separation for air circuit breaker functional units | Text |
— | Optional | The low voltage switchgear and controlgear internal separation for ACB functional units. |
| internal separation for non-air circuit breaker functional units | Text |
— | Optional | The low voltage switchgear and controlgear internal separation for non-ACB functional units. |
| isolating switching devices | Text |
— | Optional | The high-voltage switchgear and controlgear electrical endurance class of isolating switching devices in accordance with IEC 62271-103. |
| lifting device requirement | Text |
— | Optional | Specify if a lifting device, typically a wheeled hoist to facilitate the removal of functional units and associated components with a mass greater than 25 kg is to be provided by the supplier. |
| local gas pressure indication | Text |
— | Optional | The method of local gas pressure indication/alarm. |
| location in or outdoor | Text |
— | Optional | The equipment location and climate condition. |
| lower limit ambient operating temperature | Number |
degree celsius | Optional | The temperature which is the lowest ambient temperature at which a functional or physical object is expected to operate. |
| LV auxiliary compartment space heater requirement | Text |
— | Optional | Specify if a space heater is required in the low voltage auxiliary compartment. |
| LV compartments locking facility | Text |
— | Optional | The access control with regards to LV compartments covers and doors. |
| main circuit busbar insulation | Text |
— | Optional | The main circuit busbar insulation requirement. |
| main circuit earth-neutral link within incoming circuit units requirement | Text |
— | Optional | Specify if main circuit earth-neutral link within incoming circuit units is required. |
| main circuit protection for lighting and small power feeders | Text |
— | Optional | The type of short circuit protection device to be applied across all lighting and small power feeders. |
| main circuit protection for motor starters and contactor feeders | Text |
— | Optional | The type of short circuit protection device to be applied across all motor and contactor feeders. |
| main device type withdrawal requirements | Text |
— | Optional | The main device type withdrawal requirements. |
| measuring device accuracy | Text |
— | Optional | The measuring devices accuracy class. |
| mimic (synoptic) diagrams requirement | Text |
— | Optional | Specify if a mimic one-line (synoptic) diagram is to be provided on the front of the PSC-assembly, displaying the single line arrangement of busbars and the main circuit switching devices. |
| minimum motor size for space heater | Text |
kilowatt | Optional | The minimum motor size for space heater ( ≥xkW). |
| minimum spare terminal provision for future use | Text |
— | Optional | The quantity of installed spare control and auxiliary terminals for future use to be provided. |
| motor condition monitoring | Text |
— | Optional | The requirement for a motor monitoring device mounted to the motor. |
| mounting arrangement | Text |
— | Optional | Mounting arrangement in conformity with IEC 34-7 |
| multicore cable entry method | Text |
— | Optional | The multicore cable entry method. |
| nominal current | Number |
ampere | Optional | A current which is the current a functional or physical object has been designed to operate normally. |
| number of redundant communication links | Text |
— | Optional | The high-voltage switchgear and controlgear number of redundant communication links in accordance with IEC 62271-3, 6.1.3. |
| operating voltage | Number |
VOLTAG | Optional | The voltage under normal working conditions, at a given instant. |
| outgoing (load) unit direction of external conductors | Text |
— | Optional | The outgoing (load) unit direction of external conductors. |
| outgoing (load) unit external conductor type | Text |
— | Optional | The termination details for outgoing supply conductors. |
| outgoing cable entry direction | Text |
— | Optional | The required outgoing cable entry direction. |
| padlock provider | Text |
— | Optional | The padlock provider for the padlockable facilities. |
| partial discharge measurement test requirement | Text |
— | Optional | Specify where partial discharge testing of the assembly is required. |
| partition class | Text |
— | Optional | The high-voltage switchgear and controlgear switchgear partition class of the assembly in accordance with IEC 62271. |
| permissible arc duration | Number |
second | Optional | The duration of arc fault for which the assembly is rated. |
| pollution degree of macro-environment | Text |
— | Optional | The low voltage switchgear and controlgear pollution degree of macro-environment (of installation environment) in accordance with IEC 61439. |
| portable insulation fault locator requirement | Text |
— | Optional | Specify if a portable insulation fault locator is required for PSC-assemblies with unearthed electrical supplies (IT). |
| power switchgear and controlgear assembly physical configuration | Text |
— | Optional | The PSC-assembly physical access configuration. |
| process control interface communication protocol | Text |
— | Optional | The communication protocol within the PSC-assembly for the stated media interface to the process control system. |
| process control interface media | Text |
— | Optional | The communication media within the PSC-assembly for interface to the process control system. |
| process control interface network redundancy | Text |
— | Optional | The process control interface (ICSS/DCS) network redundancy. |
| protection relay type | Text |
— | Optional | The IED protection relay type. |
| provision of controlled pressure systems | Text |
— | Optional | The high-voltage switchgear and controlgear provision of controlled pressure systems. |
| provision of equipped spare functional outgoing units | Text |
— | Optional | The amount of spare functional outgoing units to be provided for future usage. |
| provision of metal oxide surge arresters | Text |
— | Optional | Specify if metal oxide surge arresters to according to IEC 60099-4 is required. |
| provision of space for future outgoing functional units | Text |
— | Optional | The amount unequipped space provision for future functional units for outgoing circuits. |
| rated current | Number |
ampere | Optional | The r.m.s. or DC value of the current for which an apparatus has been designed |
| rated duration of short circuit | Number |
second | Optional | The high-voltage switchgear and controlgear rated duration of short circuit the equipment can withstand in accordance with IEC 62271-1. |
| rated frequency | Number |
hertz | Optional | An electrical frequency of a machine at rated output |
| rated lightning impulse withstand voltage (Up) kV peak | Number |
kilovolt | Optional | The high-voltage switchgear and controlgear level of lightning over-voltages that the equipment may withstand. |
| rated peak phase to earth withstand current | Number |
kiloampere | Optional | The rated peak phase to earth withstand current the equipment can withstand. |
| rated peak withstand current | Number |
kiloampere | Optional | The rated peak withstand current for which the motor shall be rated. |
| rated short circuit current | Number |
kiloampere | Optional | The current that the functional or physical object can carry under short circuit fault conditions. |
| rated short-duration power-frequency withstand voltage (Ud) | Number |
kilovolt | Optional | The high-voltage switchgear and controlgear prescribed root mean square value of sinusoidal power frequency voltage that the equipment shall withstand during tests made under specified conditions and for a specific time. |
| rated short-time phase to earth withstand current | Number |
kiloampere | Optional | The value of rated short-time phase to earth current the equipment can withstand. |
| rated short-time withstand current | Number |
kiloampere | Optional | The root mean square value of the current which the equipment can carry in the closed position during a specified short time. |
| rated short-time withstand current time duration | Number |
second | Optional | The rated short-time withstand current (Icw) time duration. |
| rated voltage | Number |
volt | Optional | A voltage that is the voltage between lines at the terminals of the machine at rated output |
| safety shutters, disconnectors and switches locking facility | Text |
— | Optional | The locking facility with regards to safety shutters, disconnectors and switches. |
| security certification for industrial automation and control system components | Text |
— | Optional | Specify if security certification for industrial automation and control system components are required. |
| seismic activity zone | Text |
— | Optional | The seismic activity zone in accordance with IEC 60721-2-6. |
| short-circuit current in neutral conductor and in protective circuit | Number |
percent | Optional | The low voltage switchgear and controlgear short-circuit current in neutral conductor and in protective circuit in accordance with IEC 61439-1. |
| single core cable entry method | Text |
— | Optional | The single core cable entry method. |
| site pollution severity class | Text |
— | Optional | The high-voltage switchgear and controlgear site pollution severity class in accordance with IEC 62271-1 Annex K. |
| space heater control method | Text |
— | Optional | The assembly enclosure space heater control method. |
| space heater monitoring method | Text |
— | Optional | The assembly enclosure space heater monitoring method. |
| space heater requirement | Text |
— | Optional | Specify if a space heaters is required. |
| storage and handling environmental conditions | Text |
— | Optional | The storage and handling environmental conditions to determine if special packing is required. |
| supplementary conductor marking by colour | Text |
— | Optional | Specify if identification of the conductors of main and auxiliary circuits is required. |
| switch mechanical endurance class | Text |
— | Optional | The high-voltage switchgear and controlgear mechanical endurance class of isolating switching devices in accordance with IEC 62271-103. |
| system configuration of phases and wires | Text |
— | Optional | The number of phases and wires including neutral conductor. |
| test blocks requirement for air circuit breaker protection relay injection testing | Text |
— | Optional | The test block requirement for ACB protection relay injection testing. |
| thermal condition monitoring | Text |
— | Optional | Specify if an integrated thermal monitoring system is required. |
| transducer output signal | Text |
— | Optional | The transducer output for which the application requires. |
| transient overvoltages | Text |
— | Optional | The low voltage switchgear and controlgear transient overvoltage class in accordance with IEC 61439-1:2020. |
| transport and storage environmental conditions | Text |
— | Optional | Specify if transport and storage conditions are outside those specified as site conditions. |
| type of electrical connections for outgoing functional units | Text |
— | Optional | The electrical connection method for functional units for outgoing circuits with rated currents up to and including 630 A. Outgoing circuits with rated current above 630 A should be provided with withdrawable air circuit breakers (ACBs). |
| type of protection against electric shock - basic protection | Text |
— | Optional | The type of protection against electric shock – basic protection (previously protection against direct contact). |
| type of protection against electric shock - fault protection | Text |
— | Optional | The type of protection against electric shock – fault protection (previously protection against indirect contact). |
| upper limit ambient operating temperature | Number |
degree celsius | Optional | The temperature which is the highest ambient temperature at which a functional or physical object is expected to operate. |
| upper limit daily average ambient air temperature | Number |
degree celsius | Optional | The low voltage switchgear and controlgear temperature which is the highest daily average ambient air temperature at which a functional or physical object is expected to operate. |
| upper limit pitching of vessel in dynamic conditions | Text |
— | Optional | The maximum rotation about athwartship axis of the vessel under dynamic conditions defined in accordance with IEC 60092-101. |
| upper limit relative humidity | Number |
percent | Optional | The highest relative humidity at which a functional or physical object is designed for. |
| upper limit rolling of vessel in dynamic conditions | Text |
— | Optional | The maximum rotation about fore-and-aft axis of the vessel under dynamic conditions defined in accordance with IEC 60092-101. |
| voltage detecting or indicating system provision | Text |
— | Optional | Specify the voltage detecting or indicating system provision. |
| wiring insulation type | Text |
— | Optional | The auxiliary and control circuit wiring insulation type. |
| ATEX category | Text |
— | Optional | Specify in which category the physical object is divided in accordance with the directive 94/9/EC. |
| ATEX explosive atmosphere | Text |
— | Optional | Specify in which explosive atmosphere the physical object is divided in accordance with the directive 94/9/EC. |
| ATEX group | Text |
— | Optional | Specify in which group the physical object is divided in accordance with the directive 94/9/EC. |
| explosion protection concept | Text |
— | Optional | Specify the identification of electrical equipment's explosion protection and type of ignition protection in accordance with IEC/EN 60079-0. |
| explosion protection examination certificate number | Text |
— | Optional | The examination certificate number for the physical object issued by a notified body. |
| explosion protection material group | Text |
— | Optional | Specify for purposes of testing, approval, and area classification, various air mixtures (not oxygen-enriched) grouped in accordance with 500.6(A) and (B). |
| explosion protection notified body | Text |
— | Optional | The name of the nationally accredited approval body that has issued the examination certificate for the physical object. |
| permissible short-circuit current under arcing conditions (Ip arc) | Number |
kiloampere | Optional | The permissible short-circuit current the equipment can withstand under arcing condition. |