Core Ontology for Petroleum Installations · INF-UFRGS-Ontologies · CNPq INF-UFRGS-ENERGIA inf.ufrgs.br/ontologies/copi dee69df

switchgear and controlgear

CFIHOS TagAndEquipmentClass

ID: CFIHOS-30000370

Faça login para ver esta definição.

Properties / Attributes (169)
Name Data Type Unit / Valid values Required Definition
accessibility type as per IEC 62271-200 Text — Optional The high-voltage switchgear and controlgear accessibility type in accordance with IEC 62271-200.
air circuit breaker auxiliary contact provision Text — Optional The number of auxiliary contacts required for each air circuit breaker (NO-normally open, NC-normally closed).
assumed loading factor distribution - 1 circuit Text — Optional The assumed loading factor value given for a section containing only 1 distribution circuits in accordance with IEC 61439-2:2020.
assumed loading factor distribution - 10 or more circuits Text — Optional The assumed loading factor value given for a section containing more than 10 distribution circuits in accordance with IEC 61439-2:2020.
assumed loading factor distribution - 2 and 3 circuits Text — Optional The assumed loading factor value given for a section containing 2 to 3 distribution circuits in accordance with IEC 61439-2:2020.
assumed loading factor distribution - 4 and 5 circuits Text — Optional The assumed loading factor value given for a section containing 4 to 5 distribution circuits in accordance with IEC 61439-2:2020.
assumed loading factor distribution - 6 and 9 circuits Text — Optional The assumed loading factor value given for a section containing 6 to 9 distribution circuits in accordance with IEC 61439-2:2020.
assumed loading factor electric actuator (MOV) Text — Optional The assumed loading factor electric actuator (MOV).
assumed loading factor motors rated greater than 100 kW Text — Optional The assumed loading factor motors rated greater than 100 kW.
assumed loading factor motors rated less than or equal to 100 kW Text — Optional The assumed loading factor motors rated less than or equal to 100 kW.
auxiliary cable direction of external conductors Text — Optional The direction of the auxiliary cable of external conductors.
auxiliary cable entry direction Text — Optional The required auxiliary cable entry direction.
auxiliary cable external conductor type Text — Optional The conductors type of the external auxiliary cable.
auxiliary circuits voltage Number volt Optional The auxiliary circuit rated voltage.
average relative humidity Number percent Optional The high-voltage switchgear and controlgear average value of the relative humidity measured over a period of 24h in accordance with IEC 62271-1.
back-to-wall switchgear configuration required Boolean — Optional The switchgear back-to-wall configuration.
bus coupler switching device requirement Text — Optional The type of bus coupler switching device requirement.
cable termination chamber location Text — Optional The location of cable termination chamber.
capacitive breaking capability class of switches Text — Optional The high-voltage switchgear and controlgear capacitive breaking capability class of switches in accordance with IEC 62271-103.
circuit breaker condition monitoring Text — Optional Specify if an integrated circuit breaker condition monitoring system is required.
circuit breaker spring charging motors voltage Text — Optional The circuit breaker spring charging motor rated voltage.
circuit breaker switching medium Text — Optional The circuit breaker switching medium.
circuit-breaker mechanical endurance class Text — Optional The high-voltage switchgear and controlgear mechanical endurance class of circuit breakers in accordance with IEC 62271-100.
circuit-breaker restrike class Text — Optional The high-voltage switchgear and controlgear circuit-breaker restrike class in accordance with IEC 62271-100.
circuit-breaker system class Text — Optional The high-voltage switchgear and controlgear circuit-breaker system class in accordance with IEC 62271-100.
closing and opening control voltage Text — Optional The high-voltage switchgear and controlgear closing and opening control voltage in accordance with IEC 62271-1.
closing and opening indication voltage Text — Optional The high-voltage switchgear and controlgear closing and opening indication voltage in accordance with IEC 62271-1.
closing and tripping devices voltage Text — Optional The high-voltage switchgear and controlgear closing and tripping device voltage in accordance with IEC 62271-1.
communication protocol Text — Optional The digital communication system (if any), such as HART, Foundation Fieldbus or Profibus
communication protocol availability class Text — Optional The high-voltage switchgear and controlgear availability class in accordance with IEC 62271-3.
communication protocol performance class Text — Optional The high-voltage switchgear and controlgear conformance class in accordance with IEC 62271-3, 5.2.
compartment doors locking facility Text — Optional The means of access control with regards to closed compartments covers and doors.
compartment insulating medium Text — Optional The equipment technical requirement with regards to insulation medium.
conductor material Text — Optional The material of the external conductor.
conformity assessment system level Text — Optional The Conformity Assessment System (CAS) class letter in accordance with IOGP specification and obligatory requirements.
contactor control power source Text — Optional The contactor control power source configuration.
contactor switching medium Text — Optional The contactor switching medium.
country region Text — Optional Geographic location of the project within a country which will determine the applicability of local regulatory requirements.
earth fault front of compartment reset Text — Optional Specify if a earth fault front of compartment reset is required.
earthing device operator location Text — Optional The equipment's required earthing device operator location.
earthing switch mechanical endurance class Text — Optional The earthing switch mechanical endurance class.
earthing system Text — Optional The type of earthing system for which the assembly will be installed.
ECMS simulation test requirement Text — Optional Specify if an integrated internal arc-fault detection system is required.
electrical control interface media Text — Optional The electrical control interface (ECMS) media requirements.
electrical control interface network redundancy Text — Optional The electrical control interface (ECMS) network redundancy.
electrical endurance class Text — Optional The high-voltage switchgear and controlgear classification of earthing switches and circuit-breakers for short-circuit making in accordance with IEC 62271-102.
electromagnetic compatibility environment Text — Optional The low voltage switchgear and controlgear electromagnetic compatibility (EMC) environment in accordance with IEC 61439-1:2020.
elevation over mean sea level Number metre Optional Plant elevation over mean sea level.
enclosure floor surface Text — Optional Specify whether the floor surface below the installed assembly may be considered as part of the enclosure.
energy and maximum demand metering accuracy Text — Optional The energy and maximum demand metering accuracy class.
environmental location Text — Optional The environmental installation location of the equipment.
equipment access Text — Optional Specify if access to the equipment is restricted to authorized persons.
equipment integration location Text — Optional Specify if the equipment integration site differs from the end usage site, associated transport/logistic options and conditions at the integration site this shall be identified.
explosion protection gas group Text — Optional Specify the gas group classification of the physical object in accordance with IEC/EN 60079-20
explosion protection temperature class Text — Optional Specify the temperature classification of the physical object in accordance with CENELEC EN50014
explosion protection zone Text — Optional Specify the hazardous zone in which the functional or physical object is expected to operate.
explosion rated item Boolean — Optional An indicator that an equipment has been classified as safe for use in hazardous areas
facility to remotely test withdrawn functional units Text — Optional Specify if facility to remotely test withdrawn functional units are required.
glanding requirement Text — Optional Specify if special glanding is required.
HV connection compartment space heater requirement Text — Optional Specify if a space heater is required in the high voltage compartment.
IEC TR 61641:2014 arcing class Text — Optional The equipment's arcing class in accordance with IEC TR 61641:2014.
IED brand Text — Optional Specify if the IED brand is manufacturers standard or other.
IED remote configuration via ECMS Text — Optional Specify if the IED remote configuration via ECMS requirements.
IED to generator control panel interface media Text — Optional The IED to generator control panel interface media requirements.
IED to generator control panel interface protocol Text — Optional The IED to generator control panel interface protocol requirements.
IED to power management system interface media Text — Optional The IED to power management system interface media requirements.
IED to power management system interface protocol Text — Optional The IED to power management system interface protocol requirements.
IED to power management system network redundancy Text — Optional The IED to power management system interface network redundancy requirements.
impact protection Text — Optional The impact protection with regards to impact energy according to IEC 62262.
incoming (supply) unit entry of external conductors Text — Optional The incoming (supply) unit direction of external conductors.
incoming (supply) unit external conductor type Text — Optional The termination details for incoming supply conductors.
incoming cable entry direction Text — Optional The required incoming cable entry direction.
incoming unit switching device requirement Text — Optional The type of incoming unit switching device requirement.
ingress protection Text — Optional Specify the degree of ingress protection for the physical object in accordance with IEC/EN 50629 or NEMA, UL and CSA type rating.
integrated internal arc-fault detection system Text — Optional Specify if an integrated internal arc fault detection system in accordance with IEC TS 63107 is required.
interlocking / intertripping interface media Text — Optional The discrete hardwired interlocking / intertripping media requirements.
interlocking / intertripping interface protocol Text — Optional The discrete hardwired interlocking / intertripping protocol requirements.
internal arc-fault control device type Text — Optional The internal arc-fault control device type.
internal arc-fault reduction device type Text — Optional The internal arc-fault reduction device type.
internal separation for air circuit breaker functional units Text — Optional The low voltage switchgear and controlgear internal separation for ACB functional units.
internal separation for non-air circuit breaker functional units Text — Optional The low voltage switchgear and controlgear internal separation for non-ACB functional units.
isolating switching devices Text — Optional The high-voltage switchgear and controlgear electrical endurance class of isolating switching devices in accordance with IEC 62271-103.
lifting device requirement Text — Optional Specify if a lifting device, typically a wheeled hoist to facilitate the removal of functional units and associated components with a mass greater than 25 kg is to be provided by the supplier.
local gas pressure indication Text — Optional The method of local gas pressure indication/alarm.
location in or outdoor Text — Optional The equipment location and climate condition.
lower limit ambient operating temperature Number degree celsius Optional The temperature which is the lowest ambient temperature at which a functional or physical object is expected to operate.
LV auxiliary compartment space heater requirement Text — Optional Specify if a space heater is required in the low voltage auxiliary compartment.
LV compartments locking facility Text — Optional The access control with regards to LV compartments covers and doors.
main circuit busbar insulation Text — Optional The main circuit busbar insulation requirement.
main circuit earth-neutral link within incoming circuit units requirement Text — Optional Specify if main circuit earth-neutral link within incoming circuit units is required.
main circuit protection for lighting and small power feeders Text — Optional The type of short circuit protection device to be applied across all lighting and small power feeders.
main circuit protection for motor starters and contactor feeders Text — Optional The type of short circuit protection device to be applied across all motor and contactor feeders.
main device type withdrawal requirements Text — Optional The main device type withdrawal requirements.
measuring device accuracy Text — Optional The measuring devices accuracy class.
mimic (synoptic) diagrams requirement Text — Optional Specify if a mimic one-line (synoptic) diagram is to be provided on the front of the PSC-assembly, displaying the single line arrangement of busbars and the main circuit switching devices.
minimum motor size for space heater Text kilowatt Optional The minimum motor size for space heater ( ≥xkW).
minimum spare terminal provision for future use Text — Optional The quantity of installed spare control and auxiliary terminals for future use to be provided.
motor condition monitoring Text — Optional The requirement for a motor monitoring device mounted to the motor.
mounting arrangement Text — Optional Mounting arrangement in conformity with IEC 34-7
multicore cable entry method Text — Optional The multicore cable entry method.
nominal current Number ampere Optional A current which is the current a functional or physical object has been designed to operate normally.
number of redundant communication links Text — Optional The high-voltage switchgear and controlgear number of redundant communication links in accordance with IEC 62271-3, 6.1.3.
operating voltage Number VOLTAG Optional The voltage under normal working conditions, at a given instant.
outgoing (load) unit direction of external conductors Text — Optional The outgoing (load) unit direction of external conductors.
outgoing (load) unit external conductor type Text — Optional The termination details for outgoing supply conductors.
outgoing cable entry direction Text — Optional The required outgoing cable entry direction.
padlock provider Text — Optional The padlock provider for the padlockable facilities.
partial discharge measurement test requirement Text — Optional Specify where partial discharge testing of the assembly is required.
partition class Text — Optional The high-voltage switchgear and controlgear switchgear partition class of the assembly in accordance with IEC 62271.
permissible arc duration Number second Optional The duration of arc fault for which the assembly is rated.
pollution degree of macro-environment Text — Optional The low voltage switchgear and controlgear pollution degree of macro-environment (of installation environment) in accordance with IEC 61439.
portable insulation fault locator requirement Text — Optional Specify if a portable insulation fault locator is required for PSC-assemblies with unearthed electrical supplies (IT).
power switchgear and controlgear assembly physical configuration Text — Optional The PSC-assembly physical access configuration.
process control interface communication protocol Text — Optional The communication protocol within the PSC-assembly for the stated media interface to the process control system.
process control interface media Text — Optional The communication media within the PSC-assembly for interface to the process control system.
process control interface network redundancy Text — Optional The process control interface (ICSS/DCS) network redundancy.
protection relay type Text — Optional The IED protection relay type.
provision of controlled pressure systems Text — Optional The high-voltage switchgear and controlgear provision of controlled pressure systems.
provision of equipped spare functional outgoing units Text — Optional The amount of spare functional outgoing units to be provided for future usage.
provision of metal oxide surge arresters Text — Optional Specify if metal oxide surge arresters to according to IEC 60099-4 is required.
provision of space for future outgoing functional units Text — Optional The amount unequipped space provision for future functional units for outgoing circuits.
rated current Number ampere Optional The r.m.s. or DC value of the current for which an apparatus has been designed
rated duration of short circuit Number second Optional The high-voltage switchgear and controlgear rated duration of short circuit the equipment can withstand in accordance with IEC 62271-1.
rated frequency Number hertz Optional An electrical frequency of a machine at rated output
rated lightning impulse withstand voltage (Up) kV peak Number kilovolt Optional The high-voltage switchgear and controlgear level of lightning over-voltages that the equipment may withstand.
rated peak phase to earth withstand current Number kiloampere Optional The rated peak phase to earth withstand current the equipment can withstand.
rated peak withstand current Number kiloampere Optional The rated peak withstand current for which the motor shall be rated.
rated short circuit current Number kiloampere Optional The current that the functional or physical object can carry under short circuit fault conditions.
rated short-duration power-frequency withstand voltage (Ud) Number kilovolt Optional The high-voltage switchgear and controlgear prescribed root mean square value of sinusoidal power frequency voltage that the equipment shall withstand during tests made under specified conditions and for a specific time.
rated short-time phase to earth withstand current Number kiloampere Optional The value of rated short-time phase to earth current the equipment can withstand.
rated short-time withstand current Number kiloampere Optional The root mean square value of the current which the equipment can carry in the closed position during a specified short time.
rated short-time withstand current time duration Number second Optional The rated short-time withstand current (Icw) time duration.
rated voltage Number volt Optional A voltage that is the voltage between lines at the terminals of the machine at rated output
safety shutters, disconnectors and switches locking facility Text — Optional The locking facility with regards to safety shutters, disconnectors and switches.
security certification for industrial automation and control system components Text — Optional Specify if security certification for industrial automation and control system components are required.
seismic activity zone Text — Optional The seismic activity zone in accordance with IEC 60721-2-6.
short-circuit current in neutral conductor and in protective circuit Number percent Optional The low voltage switchgear and controlgear short-circuit current in neutral conductor and in protective circuit in accordance with IEC 61439-1.
single core cable entry method Text — Optional The single core cable entry method.
site pollution severity class Text — Optional The high-voltage switchgear and controlgear site pollution severity class in accordance with IEC 62271-1 Annex K.
space heater control method Text — Optional The assembly enclosure space heater control method.
space heater monitoring method Text — Optional The assembly enclosure space heater monitoring method.
space heater requirement Text — Optional Specify if a space heaters is required.
storage and handling environmental conditions Text — Optional The storage and handling environmental conditions to determine if special packing is required.
supplementary conductor marking by colour Text — Optional Specify if identification of the conductors of main and auxiliary circuits is required.
switch mechanical endurance class Text — Optional The high-voltage switchgear and controlgear mechanical endurance class of isolating switching devices in accordance with IEC 62271-103.
system configuration of phases and wires Text — Optional The number of phases and wires including neutral conductor.
test blocks requirement for air circuit breaker protection relay injection testing Text — Optional The test block requirement for ACB protection relay injection testing.
thermal condition monitoring Text — Optional Specify if an integrated thermal monitoring system is required.
transducer output signal Text — Optional The transducer output for which the application requires.
transient overvoltages Text — Optional The low voltage switchgear and controlgear transient overvoltage class in accordance with IEC 61439-1:2020.
transport and storage environmental conditions Text — Optional Specify if transport and storage conditions are outside those specified as site conditions.
type of electrical connections for outgoing functional units Text — Optional The electrical connection method for functional units for outgoing circuits with rated currents up to and including 630 A. Outgoing circuits with rated current above 630 A should be provided with withdrawable air circuit breakers (ACBs).
type of protection against electric shock - basic protection Text — Optional The type of protection against electric shock – basic protection (previously protection against direct contact).
type of protection against electric shock - fault protection Text — Optional The type of protection against electric shock – fault protection (previously protection against indirect contact).
upper limit ambient operating temperature Number degree celsius Optional The temperature which is the highest ambient temperature at which a functional or physical object is expected to operate.
upper limit daily average ambient air temperature Number degree celsius Optional The low voltage switchgear and controlgear temperature which is the highest daily average ambient air temperature at which a functional or physical object is expected to operate.
upper limit pitching of vessel in dynamic conditions Text — Optional The maximum rotation about athwartship axis of the vessel under dynamic conditions defined in accordance with IEC 60092-101.
upper limit relative humidity Number percent Optional The highest relative humidity at which a functional or physical object is designed for.
upper limit rolling of vessel in dynamic conditions Text — Optional The maximum rotation about fore-and-aft axis of the vessel under dynamic conditions defined in accordance with IEC 60092-101.
voltage detecting or indicating system provision Text — Optional Specify the voltage detecting or indicating system provision.
wiring insulation type Text — Optional The auxiliary and control circuit wiring insulation type.
ATEX category Text — Optional Specify in which category the physical object is divided in accordance with the directive 94/9/EC.
ATEX explosive atmosphere Text — Optional Specify in which explosive atmosphere the physical object is divided in accordance with the directive 94/9/EC.
ATEX group Text — Optional Specify in which group the physical object is divided in accordance with the directive 94/9/EC.
explosion protection concept Text — Optional Specify the identification of electrical equipment's explosion protection and type of ignition protection in accordance with IEC/EN 60079-0.
explosion protection examination certificate number Text — Optional The examination certificate number for the physical object issued by a notified body.
explosion protection material group Text — Optional Specify for purposes of testing, approval, and area classification, various air mixtures (not oxygen-enriched) grouped in accordance with 500.6(A) and (B).
explosion protection notified body Text — Optional The name of the nationally accredited approval body that has issued the examination certificate for the physical object.
permissible short-circuit current under arcing conditions (Ip arc) Number kiloampere Optional The permissible short-circuit current the equipment can withstand under arcing condition.

Suggest a change